⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

17.50 cal/cm^2Incident Energy at 18 in 35 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-LVMCC-5006

Protective Device: REL-UTIL-480V (Phase) (FU-UTIL-480V)


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report - edited.xls, Rev ,

Last updated: 2026-05-27 16:23 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0004. Notes: Arcing Current Low Tolerances Used; Miscoordinated, Upstream Device Tripped; NOMOTS Imported from spreadsheet Fish Trap Arc Flash Report - edited.xls. Label: # 0004. Notes: Arcing Current Low Tolerances Used; Miscoordinated, Upstream Device Tripped; NOMOTS