⚠ WARNING
Arc Flash and Electric Shock Risk
Refer to EHRA for Specific PPE Requirements
0.79 cal/cm^2Incident Energy at 18 in
14 inArc Flash Boundary
480 VACShock Risk
42 inLimited Approach
12 inRestricted Approach
Last Arc Flash Study Date: May 26, 2026
Device: B03.VMOT-302
Protective Device: CB-VMOT-301-302
Location: Fish Trap Pump Station
Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,
Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com
Notes
Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0034. Notes: Arcing Current Low Tolerances Used; NOMOTS