⚠ WARNING
Arc Flash and Electric Shock Risk
Refer to EHRA for Specific PPE Requirements
0.88 cal/cm^2Incident Energy at 36 in
30 inArc Flash Boundary
4160 VACShock Risk
60 inLimited Approach
26 inRestricted Approach
Last Arc Flash Study Date: May 26, 2026
Device: B-VFD-5003(SEC) (FU-VFD-5003(IOC) LineSide)
Protective Device: FU-VFD-5003
Location: Fish Trap Pump Station
Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,
Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com
Notes
Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0021-Line. Notes: Arcing Current Low Tolerances Used; NOMOTS