⚠ WARNING
Arc Flash and Electric Shock Risk
Refer to EHRA for Specific PPE Requirements
26.54 cal/cm^2Incident Energy at 36 in
259 inArc Flash Boundary
4160 VACShock Risk
60 inLimited Approach
26 inRestricted Approach
Last Arc Flash Study Date: May 26, 2026
Device: B-UTIL (REL-UTIL-4160V LineSide)
Protective Device: MaxTripTime @2.0s
Location: Fish Trap Pump Station
Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,
Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com
Notes
Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0019-Line. Notes: < 80% Cleared Fault Threshold; Max Arcing Duration Reached; Base Project