⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

1.41 cal/cm^2Incident Energy at 18 in 20 inArc Flash Boundary 208 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-PNL-HT

Protective Device: CB-PNL-HT


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0013. Notes: Arcing Current Low Tolerances Used; Sustainable arc in 240V or less and bolted fault current < 2000 A is less likely to occur (IEEE 1584-2018 Section 4.3); NOMOTS