Fish Trap Pump Station

Active arc flash labels for this site.

Reset
⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.10 cal/cm^2Incident Energy at 18 in 4 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-DS-5015

Protective Device: CB-XFMR-5015


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0001. Notes: Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.08 cal/cm^2Incident Energy at 36 in 7 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-LR-5005(INPUT)

Protective Device: FU-VFD-5003(IOC)


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0002. Notes: Current Limiting Fuse; Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.30 cal/cm^2Incident Energy at 36 in 15 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-LR-5005(OUTPUT)

Protective Device: FU-004A


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0003. Notes: P-004-ON-VFD

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

17.50 cal/cm^2Incident Energy at 18 in 35 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-LVMCC-5006

Protective Device: REL-UTIL-480V (Phase) (FU-UTIL-480V)


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report - edited.xls, Rev ,

Last updated: 2026-05-27 16:23 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0004. Notes: Arcing Current Low Tolerances Used; Miscoordinated, Upstream Device Tripped; NOMOTS Imported from spreadsheet Fish Trap Arc Flash Report - edited.xls. Label: # 0004. Notes: Arcing Current Low Tolerances Used; Miscoordinated, Upstream Device Tripped; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

12.60 cal/cm^2Incident Energy at 36 in 82 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MCC-5002

Protective Device: REL-GE-750 (Phase)


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report - edited.xls, Rev ,

Last updated: 2026-05-27 16:23 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0004. Notes: Base Project Imported from spreadsheet Fish Trap Arc Flash Report - edited.xls. Label: # 0004. Notes: Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

1.20 cal/cm^2Incident Energy at 36 in 15 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MCC-5003

Protective Device: FU-004A


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report - edited.xls, Rev ,

Last updated: 2026-05-27 16:23 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0005. Notes: P-004-ON-VFD Imported from spreadsheet Fish Trap Arc Flash Report - edited.xls. Label: # 0005. Notes: P-004-ON-VFD

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

3.49 cal/cm^2Incident Energy at 18 in 35 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MCC-5006 (CB-LVMCC-5006 LineSide)

Protective Device: REL-UTIL-480V (Phase) (FU-UTIL-480V)


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0007-Line. Notes: Arcing Current Low Tolerances Used; Miscoordinated, Upstream Device Tripped; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.12 cal/cm^2Incident Energy at 36 in 52 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MCC-P-002

Protective Device: FU-002B


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0007. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.12 cal/cm^2Incident Energy at 36 in 52 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MCC-P-003

Protective Device: FU-003B


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0008. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.12 cal/cm^2Incident Energy at 36 in 52 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MCC-P-004

Protective Device: FU-004B


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0009. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.35 cal/cm^2Incident Energy at 36 in 55 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MOT-P-002

Protective Device: FU-002B


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0010. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.32 cal/cm^2Incident Energy at 36 in 55 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MOT-P-003

Protective Device: FU-003B


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0011. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.29 cal/cm^2Incident Energy at 36 in 54 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-MOT-P-004

Protective Device: FU-004B


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0012. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

1.41 cal/cm^2Incident Energy at 18 in 20 inArc Flash Boundary 208 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-PNL-HT

Protective Device: CB-PNL-HT


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0013. Notes: Arcing Current Low Tolerances Used; Sustainable arc in 240V or less and bolted fault current < 2000 A is less likely to occur (IEEE 1584-2018 Section 4.3); NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.50 cal/cm^2Incident Energy at 18 in 28 inArc Flash Boundary 208 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-PNL-MB (CB-PNL-MB LoadSide)

Protective Device: CB-PNL-MB


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0015-Load. Notes: Max Arcing Duration Reached; Sustainable arc in 240V or less and bolted fault current < 2000 A is less likely to occur (IEEE 1584-2018 Section 4.3); Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.88 cal/cm^2Incident Energy at 18 in 15 inArc Flash Boundary 208 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-PNL-VCTL52

Protective Device: CB-PNL-VCTL52


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0015. Notes: Arcing Current Low Tolerances Used; Sustainable arc in 240V or less and bolted fault current < 2000 A is less likely to occur (IEEE 1584-2018 Section 4.3); NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

5.12 cal/cm^2Incident Energy at 36 in 91 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-SWGR-5001

Protective Device: REL-UTIL-4160V (Phase)


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0013. Notes: Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

5.17 cal/cm^2Incident Energy at 36 in 91 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-UTC-INC

Protective Device: REL-UTIL-4160V (Phase)


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0018. Notes: Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

26.54 cal/cm^2Incident Energy at 36 in 259 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-UTIL (REL-UTIL-4160V LineSide)

Protective Device: MaxTripTime @2.0s


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0019-Line. Notes: < 80% Cleared Fault Threshold; Max Arcing Duration Reached; Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.88 cal/cm^2Incident Energy at 36 in 30 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-VFD-5003(PRI)

Protective Device: FU-VFD-5003


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0016. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.88 cal/cm^2Incident Energy at 36 in 30 inArc Flash Boundary 4160 VACShock Risk 60 inLimited Approach 26 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-VFD-5003(SEC) (FU-VFD-5003(IOC) LineSide)

Protective Device: FU-VFD-5003


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0021-Line. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.02 cal/cm^2Incident Energy at 18 in 1 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-XFMR-5015(PRI)

Protective Device: FU-DS-5015


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0018. Notes: Current Limiting Fuse; Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.52 cal/cm^2Incident Energy at 18 in 29 inArc Flash Boundary 208 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B-XFMR-5015(SEC)

Protective Device: CB-XFMR-5015 (FU-DS-5015)


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0019. Notes: Miscoordinated, Upstream Device Tripped; Max Arcing Duration Reached; Sustainable arc in 240V or less and bolted fault current < 2000 A is less likely to occur (IEEE 1584-2018 Section 4.3); Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.69 cal/cm^2Incident Energy at 18 in 13 inArc Flash Boundary 208 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.HTR-MB

Protective Device: CB-HTR-MB


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0023. Notes: Arcing Current Low Tolerances Used; Sustainable arc in 240V or less and bolted fault current < 2000 A is less likely to occur (IEEE 1584-2018 Section 4.3); NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.21 cal/cm^2Incident Energy at 18 in 6 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.HVAC1

Protective Device: CB-HVAC1


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0020. Notes: Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.20 cal/cm^2Incident Energy at 18 in 6 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.HVAC2

Protective Device: CB-HVAC2


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0021. Notes: Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

1.17 cal/cm^2Incident Energy at 18 in 18 inArc Flash Boundary 208 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.LPA

Protective Device: CB-XFMR-LPA


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0022. Notes: Max Arcing Duration Reached; Sustainable arc in 240V or less and bolted fault current < 2000 A is less likely to occur (IEEE 1584-2018 Section 4.3); NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.28 cal/cm^2Incident Energy at 18 in 7 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.MOT-15

Protective Device: CB-SUMP-PUMP


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0023. Notes: Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

2.50 cal/cm^2Incident Energy at 18 in 28 inArc Flash Boundary 208 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.PNL-MB

Protective Device: CB-PNL-MB


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0024. Notes: Max Arcing Duration Reached; Sustainable arc in 240V or less and bolted fault current < 2000 A is less likely to occur (IEEE 1584-2018 Section 4.3); Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.56 cal/cm^2Incident Energy at 18 in 11 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.VFD-CAB

Protective Device: CB-VFD-CAB


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0025. Notes: Base Project

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.48 cal/cm^2Incident Energy at 18 in 11 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.VMOT-13

Protective Device: CB-VMOT-13-14


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0026. Notes: Out of IEEE 1584 kA Range. Lee Equation Used. Consider NESC/EPRI method to compare; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.48 cal/cm^2Incident Energy at 18 in 11 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.VMOT-14

Protective Device: CB-VMOT-13-14


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0027. Notes: Out of IEEE 1584 kA Range. Lee Equation Used. Consider NESC/EPRI method to compare; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.47 cal/cm^2Incident Energy at 18 in 11 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B.VMOT-44A

Protective Device: CB-VMOT-44A


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0028. Notes: Out of IEEE 1584 kA Range. Lee Equation Used. Consider NESC/EPRI method to compare; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.78 cal/cm^2Incident Energy at 18 in 14 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B02.VMOT-201

Protective Device: CB-VMOT-201-202


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0029. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.79 cal/cm^2Incident Energy at 18 in 14 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B02.VMOT-201-202

Protective Device: CB-VMOT-201-202


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0030. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.78 cal/cm^2Incident Energy at 18 in 14 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B02.VMOT-202

Protective Device: CB-VMOT-201-202


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0031. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.79 cal/cm^2Incident Energy at 18 in 14 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B03.VMOT-301

Protective Device: CB-VMOT-301-302


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0032. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.78 cal/cm^2Incident Energy at 18 in 14 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B03.VMOT-301-302

Protective Device: CB-VMOT-301-302


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0033. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.79 cal/cm^2Incident Energy at 18 in 14 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B03.VMOT-302

Protective Device: CB-VMOT-301-302


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0034. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.79 cal/cm^2Incident Energy at 18 in 14 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B04.VMOT-401

Protective Device: CB-VMOT-401-402


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0035. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.73 cal/cm^2Incident Energy at 18 in 13 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B04.VMOT-401-402

Protective Device: CB-VMOT-401-402


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0036. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.79 cal/cm^2Incident Energy at 18 in 14 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: B04.VMOT-402

Protective Device: CB-VMOT-401-402


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0037. Notes: Arcing Current Low Tolerances Used; NOMOTS

Open Label

⚠ WARNING

Arc Flash and Electric Shock Risk

Refer to EHRA for Specific PPE Requirements

0.76 cal/cm^2Incident Energy at 18 in 13 inArc Flash Boundary 480 VACShock Risk 42 inLimited Approach 12 inRestricted Approach

Last Arc Flash Study Date: May 26, 2026

Device: BST.VMOT-13-14

Protective Device: CB-VMOT-13-14


Location: Fish Trap Pump Station

Source Drawing: Fish Trap Arc Flash Report.xls, Rev ,

Last updated: 2026-05-27 16:08 UTC by jacob.posch@fhr.com

Notes

Imported from spreadsheet Fish Trap Arc Flash Report.xls. Label: # 0038. Notes: NOMOTS

Open Label